Utilization of Rainwater for Fire Extinguishing Systems with Hydrants and Sprinklers at the Regional Office Building I of Bank Tabungan Negara, Bandung City
DOI:
https://doi.org/10.33603/jki.v13i3.10692Keywords:
Rainwater utilization, Hydrants, SprinklersAbstract
Office buildings require security systems to ensure comfort, such as fire protection systems, including adequate water supply. This research implements rainwater harvesting as an alternative source for more efficient water resource management and modifies the piping system for hydrants and sprinklers. In this study, a hydrological analysis was conducted based on rainfall data in Bandung City from 2014 to 2024, assessing the water needs for hydrants and sprinklers, as well as analyzing the plans for filtration, pumping, and storage tanks for the rainwater harvesting system. This research utilizes a storage tank with a capacity of 128 m³ and employs Nanotec filtration using FRP filter media, along with a pump capacity of 125-139 m, operating on power ranging from 110-132 kW. The results of the study indicate that the availability of harvested rainwater reaches 55% of the requirements for hydrants and sprinklers.
References
[1] Ha, Park Eun, Gatot Eko Susilo and Endro Prasetyo Wahono “Perencanaan Sistem Pemanenan Air Hujan Skala Rumah Tangga Di Korea Selatan” Lampung, 2018.
[2] SNI 03-1745-1989 “Tata Cara Perencanan dan Pemasangan Sistem Pipa Tegak dan Slang untuk Pencegahan Bahaya Kebakaran pada Bangunan Rumah dan Gedung” 1989.
[3] SNI 03-3989-2000 “Tata cara perencanaan dan pemasangan sistem springkler otomatik untuk pencegahan bahaya kebakaran pada bangunan gedung.” 2000.
[4] Okta, Pindra “Perencanaan Panen Air Hujan Sebagai Sumber Air Alternatif Pada Fakultas Teknik Program Studi Teknik Sipil Universitas Islam Riau Pekanbaru” Riau, 2021.
[5] Maulina, Anandha “STUDI PEMANFAATAN AIR HUJAN SEBAGAI SUMBER AIR BAKU UNTUK AIR BERSIH PADA KAMPUS UNIVERSITAS BOSOWA MAKASSAR” Makassar, 2023.
[6] SNI-03-1735-2000 “Tata Cara Perencanaan Akses bangunan dan Akses Lingkungan Untuk Pencegahan Bahaya Kebakaran pada Bangunan Gedung” 2000.
[7] M.A.F, Muhammad Kahfi and M. Putra Amanullah “PEMANFAATAN AIR HUJAN SEBAGAI SISTEM PROTEKSI KEBAKARAN AKTIF PADA PROYEK GEDUNG BARU FAKULTAS KEDOKTERAN UNIVERSITAS JENDERAL ACHMAD YANI.”
[8] sni_pipa_1745_2000 “Tata Cara Perencanaan dan Pemasangan Sistem Pipa Tegak dan Slang untuk Pencegahan Bahaya Kebakaran pada Bangunan Rumah dan Gedung” 2000.
[9] “Sistem plambing pada bangunan gedung,” 2015, [Online]. Available: www.bsn.go.id
[10] NFPA 13 “Standard For the Installation Of Sprinkler Systems” 2013 Edition. National Fire Protection Association.
Downloads
Published
Issue
Section
License
- Authors retain copyright and grant the journal right of first publication with the work simultaneously licensed under a Creative Commons Attribution-ShareAlike 4.0 International License that allows others to share and adapt the work with an acknowledgement of the works authorship and initial publication in this journal.